PACi Standard Ceiling • R32
14.0 kW
Kit KIT-140PT2Z5
Remote controller CZ-RTC5B
Cooling capacity (Nominal) kW 14,0
Cooling capacity (Min) kW 3,3
Cooling capacity (Max) kW 15,0
EER (Nominal) (1) W/W 2,98
EER (Min) (1) W/W 5,32
EER (Max) (1) W/W 2,73
SEER (2) 5,5
Pdesign (cooling) kW 14,0
Input power cooling (Nominal) kW 4,70
Input power cooling (Min) kW 0,62
Input power cooling (Max) kW 5,50
Annual energy consumption cooling (3) kWh/a 1530
Heating capacity (Nominal) kW 14,0
Heating capacity (Min) kW 3,4
Heating capacity (Max) kW 16,0
COP (Nominal) (1) W/W 3,70
COP (Min) (1) W/W 5,48
COP (Max) (1) W/W 3,08
SCOP (2) 3,7
Pdesign at -10°C kW 13,6
Input power heating (Nominal) kW 3,78
Input power heating (Min) kW 0,62
Input power heating (Max) kW 5,20
Annual energy consumption heating (3) kWh/a 5153
Indoor unit S-140PT2E5B
Indoor air flow (Hi) m³/min 35,0
Indoor air flow (Med) m³/min 29,0
Indoor air flow (Lo) m³/min 25,0
Moisture removal volume L/h 9,0
Indoor sound pressure (Med) (4) dB(A) 41
Indoor sound pressure (Lo) (4) dB(A) 37
Indoor sound power (Hi) dB(A) 65
Indoor sound power (Med) dB(A) 59
Indoor sound power (Lo) dB(A) 55
Indoor dimension (Height) mm 235
Indoor dimension (Width) mm 1590
Indoor dimension (Depth) mm 690
Indoor net weight kg 40
Outdoor unit U-140PZ2E5
Outdoor power source V 220 - 230 - 240
Current in cooling (1p 220V / 3p 380) A 22,10
Current in cooling (1p 230V / 3p 400) A 21,20
Current in cooling (1p 240V / 3p 415) A 20,30
Current in heating (1p 220V / 3p 380) A 17,70
Current in heating (1p 230V / 3p 400) A 16,90
Current in heating (1p 240V / 3p 415) A 16,20
Outdoor air flow (Cool) m³/min 89
Outdoor air flow (Heat) m³/min 83
Outdoor sound pressure (Cool -Hi) dB(A) 56
Outdoor sound pressure (Heat -Hi) dB(A) 56
Outdoor sound power (Cool -Hi) dB(A) 74
Outdoor sound power (Heat -Hi) dB(A) 74
Outdoor dimension (Height) mm 996
Outdoor dimension (Width) mm 980
Outdoor dimension (Depth) mm 370
Outdoor net weight kg 94
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88)
Pipe length range m 5 ~ 50
Elevation difference (in/out) (5) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 45
Refrigerant (R32) / CO2 Eq. kg / T 2,98 / 2,0115
Operating range (Cool - Min) °C -10
Operating range (Cool - Max) °C 43
Operating range (Heat - Min) °C -15
Operating range (Heat - Max) °C 24

(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the SEER and SCOP is calculated based on values of EU/2281/2016.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) The sound pressure of the units shows the value measured of the position 1 m in front of the main body and 1 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(5) When installing the outdoor unit at a higher position than the indoor unit.
* Recommended fuse for the indoor 3 A.