T-CAP samostalna vanjska M serija s kontrolnim modulom 1 faza - 3 faze · R290

Serija Aquarea M, najnovija generacija Aquarea dizalica topline zrak-voda s R290

Aquarea T-CAP M serija donosi revoluciju u dizajnu, izvedbi, povezivosti i održivosti

Rješenje je prikladno i za nove zgrade i za naknadnu ugradnju, budući da nudi održivu alternativu tradicionalnim sustavima grijanja na fosilna goriva i može se lako integrirati s postojećim sustavom vode kao što su ventilokonvektori, podno grijanje ili spremnici kućne tople vode.

Specifikacije

Prikaži sve
T-CAP samostalna vanjska M serija s kontrolnim modulom 1 faza - 3 faze · R290
20 kW
Outdoor unit WH-WXG20ME8
Heating capacity (A +7°C, W 35°C) kW 20,00
COP (A +7°C, W 35°C) 4,80
Heating capacity (A +7°C, W 55°C) kW 20,00
COP (A +7°C, W 55°C) 3,18
Heating capacity (A +2°C, W 35°C) kW 20,00
COP (A +2°C, W 35°C) 3,39
Heating capacity (A +2°C, W 55°C) kW 20,00
COP (A +2°C, W 55°C) 2,08
Heating capacity (A -7°C, W 35°C) kW 20,00
COP (A -7°C, W 35°C) 2,48
Heating capacity (A -7°C, W 55°C) kW 20,00
COP (A -7°C, W 55°C) 1,90
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 4,36 / 3,59
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 171 / 141
Heating average climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A++/A++
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 5,37 / 4,07
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 212 / 160
Heating warm climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+++ / A+++
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 3,07 / 2,57
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 120 / 100
Heating cold climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A / A+
Outdoor dimension (Height) mm 1.645
Outdoor dimension (Width) mm 1.500
Outdoor dimension (Depth) mm 460
Outdoor net weight kg 240
A class pump (Number of speeds) Promjenjiva brzina
A class pump (Input power Min) W 230
Heating water flow (∆T=5 K. 35°C) L/min 57,3
Operation range - Outdoor ambient (Heat) °C -25 ~ +35
Operation range - Outdoor ambient (Cool) °C +10 ~ +43
Water outlet (Heat) °C 20 ~ 75 (4)
Water outlet (Cool) °C 5 ~ 20
Indoor dimension (Height) mm 450
Indoor dimension (Width) mm 450
Indoor dimension (Depth) mm 116
Indoor net weight kg 7

(1) Ljestvica od A+++ do D.
(2) Razina zvučne snage u skladu s EN12102 prema uvjetima EN14825.
(3) Modeli WH-WXG su hermetički zatvoreni.
(4) Provjerite lokalne propise.
* Klasifikacija EER i COP je samo na 230V u skladu s EU direktivom 2003/32/EC.