T-CAP stand-alone outdoor M Series 1 phase - 3 phase · R290

Aquarea M Series, the latest generation of Aquarea air to water heat pumps with R290

Aquarea T‑CAP M Series delivers a revolution in the design, performance, connectivity, and sustainability

The solution is suitable for both new buildings and retrofits, as it offers a sustainable alternative to traditional fossil fuel heating systems and it can be easily integrated with existing water system such as fan coils, floor heating or domestic hot water tanks.

1) Down to 15ºC outdoor for 20, 25 and 30kW models
2) Sound pressure calculation for WH-WXG12ME5, free standing, A +7°C, W 35°C in Quite mode 3
3) Down to -25ºC outdoor for 20, 25 and 30kW models

Specifications

See all
T-CAP stand-alone outdoor M Series 1 phase - 3 phase · R290 SINGLE PHASE THREE PHASE
9 kW 12 kW 9 kW 12 kW 16 kW 20 kW 25 kW 30 kW
Outdoor unit WH-WXG09ME5 WH-WXG12ME5 WH-WXG09ME8 WH-WXG12ME8 WH-WXG16ME8 WH-WXG20ME8 WH-WXG25ME8 WH-WXG30ME8
Remote controller with Wi-Fi adapter CZ-RTW2TAW1C CZ-RTW2TAW1C CZ-RTW2TAW1C CZ-RTW2TAW1C CZ-RTW2TAW1C CZ-RTW2TAW1C CZ-RTW2TAW1C CZ-RTW2TAW1C
Heating capacity (A +7°C, W 35°C) kW 9,00 12,00 9,00 12,00 16,00 20,00 25,00 30,00
COP (A +7°C, W 35°C) 5,23 5,06 5,23 5,06 4,89 4,80 4,50 4,40
Heating capacity (A +7°C, W 55°C) kW 9,00 12,00 9,00 12,00 16,00 20,00 25,00 30,00
COP (A +7°C, W 55°C) 3,24 3,23 3,24 3,23 3,20 3,18 3,00 3,00
Heating capacity (A +2°C, W 35°C) kW 9,00 12,00 9,00 12,00 16,00 20,00 25,00 30,00
COP (A +2°C, W 35°C) 3,81 3,54 3,81 3,54 3,30 3,39 2,80 2,50
Heating capacity (A +2°C, W 55°C) kW 9,00 12,00 9,00 12,00 16,00 20,00 25,00 30,00
COP (A +2°C, W 55°C) 2,54 2,42 2,54 2,42 2,37 2,08 1,97 1,95
Heating capacity (A -7°C, W 35°C) kW 9,00 12,00 9,00 12,00 16,00 20,00 25,00 30,00
COP (A -7°C, W 35°C) 3,45 3,00 3,45 3,00 2,53 2,48 2,36 2,33
Heating capacity (A -7°C, W 55°C) kW 9,00 12,00 9,00 12,00 16,00 20,00 25,00 30,00
COP (A -7°C, W 55°C) 2,35 2,17 2,35 2,17 1,97 1,90 1,80 1,49
Cooling capacity (A 35°C, W 7°C) kW 9,00 9,00 9,00 9,00 9,00
EER (A 35°C, W 7°C) 3,61 3,61 3,61 3,61 3,61
Cooling capacity (A 35°C, W 18°C) kW 9,00 12,00 9,00 12,00 16,00
EER (A 35°C, W 18°C) 5,26 5,26 5,26 5,26 5,26
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 4,96 / 3,57 5,00 / 3,46 4,96 / 3,57 5,00 / 3,46 4,20 / 3,31 4,36 / 3,59 4,25 / 3,57 3,95 / 3,46
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 195 / 140 197 / 135 195 / 140 197 / 135 168 / 129 171 / 141 167 / 140 155 / 135
Heating average climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+++ / A++ A+++ / A++ A+++ / A++ A+++ / A++ A+++ / A++ A++/A++ A++/A++ A++/A++
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 6,47 / 4,34 6,47 / 4,34 6,47 / 4,34 6,47 / 4,34 5,88 / 4,09 5,37 / 4,07 5,22 / 4,14 4,93 / 4,01
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 256 / 171 256 / 171 256 / 171 256 / 171 232 / 160 212 / 160 206 / 163 194 / 158
Heating warm climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) SCOP 4,31 / 3,26 4,31 / 3,26 4,31 / 3,26 4,31 / 3,26 3,83 / 3,20 3,07 / 2,57 3,16 / 2,71 3,20 / 2,71
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) ηs % 169 / 127 169 / 127 169 / 127 169 / 127 150 / 125 120 / 100 123 / 105 125 / 105
Heating cold climate. Energy class (W 35°C / W 55°C) (1) A+++ to D A++ / A++ A++ / A++ A++ / A++ A++ / A++ A++ / A++ A / A+ A+ / A+ A+ / A+
Outdoor sound power (Heat) (2) dB(A) 52 53 52 53 57 56 59 61
Outdoor dimension (Height) mm 1.520 1.520 1.520 1.520 1.520 1.645 1.645 1.645
Outdoor dimension (Width) mm 1.200 1.200 1.200 1.200 1.200 1.500 1.500 1.500
Outdoor dimension (Depth) mm 430 430 430 430 430 460 460 460
Outdoor net weight kg 161 161 161 161 165 240 240 240
A class pump (Number of speeds) Variable speed Variable speed Variable speed Variable speed Variable speed Variable speed Variable speed Variable speed
A class pump (Input power Min) W 30 30 30 30 30 230 230 230
A class pump (Input power Max) W 175 175 175 175 175
Heating water flow (∆T=5 K. 35°C) L/min 25,8 34,4 25,8 34,4 45,9 57,3 71,6 86,0
Refrigerant (R290) / CO2 Eq. (3) kg / T 1,78 / 0,006 1,78 / 0,006 1,78 / 0,006 1,78 / 0,006 1,77 / 0,006 3,0 / 0,009 3,0 / 0,009 3,0 / 0,009
Operation range - Outdoor ambient (Heat) °C -28 ~ +35 -28 ~ +35 -28 ~ +35 -28 ~ +35 -28 ~ +35 -25 ~ +35 -25 ~ +35 -25 ~ +35
Operation range - Outdoor ambient (Cool) °C +10 ~ +43 +10 ~ +43 +10 ~ +43 +10 ~ +43 +10 ~ +43 +10 ~ +43 +10 ~ +43 +10 ~ +43
Water outlet (Heat) °C 25 ~ 75 25 ~ 75 25 ~ 75 25 ~ 75 25 ~ 75 20 ~ 75 (4) 20 ~ 75 (4) 20 ~ 75 (4)
Water outlet (Cool) °C 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20 5 ~ 20
Recommended RCD, supply A 30 30 20 20 25
Indoor recommended minimum cable size, supply (4) mm² 3x4,0 3x4,0 5x1,5 5x1,5 5x2,5

(1) Scale from A+++ to D.
(2) Sound power level in accordance to EN12102 under conditions of the EN14825.
(3) WH-WXG models are hermetically sealed.
(4) Check local regulations.
* EER and COP classification is at 230V only in accordance with EU directive 2003/32/EC.