Models
Advanced energy recovery ventilation ZY Series
- Recovers up to 83% of the heat in the outgoing air
- 9 model line-up including 2.000m³/h model
- DC motors
- ESP up to 150Pa
- An effective F7 grade filter built-in as a standard
- Intuitive remote controller with RS485 connection
Best efficiency ECOi Series
Specifications
Advanced ERV ZY Series | SINGLE PHASE | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
150 m³/h | 250 m³/h | 350 m³/h | 500 m³/h | 650 m³/h | 800 m³/h | 1.000 m³/h | 1.500 m³/h | 2.000 m³/h | |||
Indoor unit | FV-15ZY1G (1) | FV-25ZY1G (1) | FV-35ZY1G (1) | FV-50ZY1G (1) | FV-65ZY1G (1) | FV-80ZY1G (1) | FV-1KZY1G (1) | FV-1HZY1G (1) | FV-2KZY1G (1) | ||
Power supply (Voltage) | V | 220 - 240 | 220 - 240 | 220 - 240 | 220 - 240 | 220 - 240 | 220 - 240 | 220 - 240 | 220 - 240 | 220 - 240 | |
Power supply (Phase) | 1φ | 1φ | 1φ | 1φ | 1φ | 1φ | 1φ | 1φ | 1φ | ||
Power supply (Frequency) | Hz | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | |
Motor type | DC | DC | DC | DC | DC | DC | DC | DC | DC | ||
ERV - Air flow (Max) | m³/h | 150 | 250 | 350 | 500 | 650 | 800 | 1.000 | 1.500 | 2.000 | |
ERV - External static pressure (Max) | Pa | 100 | 120 | 140 | 130 | 150 | 150 | 150 | 130 | 130 | |
ERV - Sound power (Max) (2) | dB(A) | 37 | 38 | 39 | 43 | 45 | 45 | 46 | 49 | 51 | |
ERV - Input power (Max) | W | 76 ~ 84 | 106 ~ 117 | 141 ~ 155,5 | 180 ~ 198 | 420 ~ 462 | 470 ~ 517 | 550 ~ 605 | 940 ~ 1.034 | 1.100 ~ 1.210 | |
Heat exchange efficiency - Cooling (Max) (3) | % | 68,0 | 69,0 | 71,0 | 65,0 | 64,0 | 63,0 | 65,0 | 63,0 | 65,0 | |
Heat exchange efficiency - Heating (Max) (3) | % | 83,0 | 82,0 | 83,0 | 81,0 | 82,0 | 83,0 | 82,0 | 83,0 | 82,0 | |
Enthalpy exchange efficiency - Cooling (Max) | % | 66,0 | 66,0 | 67,0 | 62,5 | 62,5 | 63,5 | 63,0 | 63,5 | 63,0 | |
Enthalpy exchange efficiency - Heating (Max) | % | 76,0 | 74,0 | 75,0 | 73,0 | 72,0 | 73,0 | 74,0 | 73,0 | 74,0 | |
Adapter diameter | mm | 100 | 150 | 150 | 200 | 200 | 250 | 250 | 250 | 250 | |
Dimension (Height) | mm | 289 | 289 | 331 | 331 | 404 | 404 | 404 | 808 | 808 | |
Dimension (Width) | mm | 610 | 735 | 874 | 1.016 | 954 | 1.004 | 1.231 | 1.004 | 1.231 | |
Dimension (Depth) | mm | 860 | 860 | 968 | 968 | 1.008 | 1.224 | 1.224 | 1.224 | 1.224 | |
Net weight | kg | 23 | 27 | 37 | 40 | 48 | 60 | 64 | 119 | 142 |
(1) Different dimensions depending on models.
(2) Measurement of noise 1,5m below the center of the main unit (anechoic chamber).
(3) Heat exchange efficiency measurement standard JIS B 8628 (2003).
* JIS B 8628 (2017) is used in the measurement environment.