T-CAP stand-alone outdoor M Series 1 phase - 3 phase · R290
Aquarea M Series, the latest generation of Aquarea air to water heat pumps with R290
Aquarea T‑CAP M Series delivers a revolution in the design, performance, connectivity, and sustainability
The solution is suitable for both new buildings and retrofits, as it offers a sustainable alternative to traditional fossil fuel heating systems and it can be easily integrated with existing water system such as fan coils, floor heating or domestic hot water tanks.
- Up to 75°C water outlet down to -15°C outdoor 1)
- Quiet operation: Only 29dB(A) sound pressure at 5m 2)
- Reliable outdoor units with Panasonic compressor, operating down to -28°C outdoor 3)
- T-CAP technology: Keeping heating capacity down to -20°C
- Panasonic Comfort Cloud App and Aquarea Service Cloud included
1) Down to 15ºC outdoor for 20, 25 and 30kW models
2) Sound pressure calculation for WH-WXG12ME5, free standing, A +7°C, W 35°C in Quite mode 3
3) Down to -25ºC outdoor for 20, 25 and 30kW models
Specifications
T-CAP stand-alone outdoor M Series 1 phase - 3 phase · R290 | |||
---|---|---|---|
30 kW | |||
Outdoor unit | WH-WXG30ME8 | ||
Heating capacity (A +7°C, W 35°C) | kW | 30,00 | |
COP (A +7°C, W 35°C) | 4,40 | ||
Heating capacity (A +7°C, W 55°C) | kW | 30,00 | |
COP (A +7°C, W 55°C) | 3,00 | ||
Heating capacity (A +2°C, W 35°C) | kW | 30,00 | |
COP (A +2°C, W 35°C) | 2,50 | ||
Heating capacity (A +2°C, W 55°C) | kW | 30,00 | |
COP (A +2°C, W 55°C) | 1,95 | ||
Heating capacity (A -7°C, W 35°C) | kW | 30,00 | |
COP (A -7°C, W 35°C) | 2,33 | ||
Heating capacity (A -7°C, W 55°C) | kW | 30,00 | |
COP (A -7°C, W 55°C) | 1,49 | ||
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) | SCOP | 3,95 / 3,46 | |
Heating average climate. Seasonal energy efficiency (W 35°C / W 55°C) | ηs % | 155 / 135 | |
Heating average climate. Energy class (W 35°C / W 55°C) (1) | A+++ to D | A++/A++ | |
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) | SCOP | 4,93 / 4,01 | |
Heating warm climate. Seasonal energy efficiency (W 35°C / W 55°C) | ηs % | 194 / 158 | |
Heating warm climate. Energy class (W 35°C / W 55°C) (1) | A+++ to D | A+++ / A+++ | |
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) | SCOP | 3,20 / 2,71 | |
Heating cold climate. Seasonal energy efficiency (W 35°C / W 55°C) | ηs % | 125 / 105 | |
Heating cold climate. Energy class (W 35°C / W 55°C) (1) | A+++ to D | A+ / A+ | |
Outdoor dimension (Height) | mm | 1.645 | |
Outdoor dimension (Width) | mm | 1.500 | |
Outdoor dimension (Depth) | mm | 460 | |
Outdoor net weight | kg | 240 | |
A class pump (Number of speeds) | Variable speed | ||
A class pump (Input power Min) | W | 230 | |
Heating water flow (∆T=5 K. 35°C) | L/min | 86,0 | |
Operation range - Outdoor ambient (Heat) | °C | -25 ~ +35 | |
Operation range - Outdoor ambient (Cool) | °C | +10 ~ +43 | |
Water outlet (Heat) | °C | 20 ~ 75 (4) | |
Water outlet (Cool) | °C | 5 ~ 20 |
(1) Scale from A+++ to D.
(2) Sound power level in accordance to EN12102 under conditions of the EN14825.
(3) WH-WXG models are hermetically sealed.
(4) Check local regulations.
* EER and COP classification is at 230V only in accordance with EU directive 2003/32/EC.