PACi NX Series Elite 4 way 90x90 cassette Inverter+ - R32

4 way 90x90 cassette - PU3

Powerful turbo fan and intelligent Econavi sensor ensure high energy efficiency, and nanoe™ X which is equipped as standard provides an exceptional level of indoor air quality.

The next generation of commercial air conditioners is here

Specifications

See all
PACi NX Series Elite 4 way 90x90 cassette Inverter+ - R32
7.1 kW
Kit KIT-71PU3ZH45
Remote controller CZ-RTC5B
Cooling capacity (Nominal) kW 7,1
Cooling capacity (Min) kW 2,2
Cooling capacity (Max) kW 9,0
EER (Nominal) (1) W/W 4,06
EER (Min) (1) W/W 2,69
EER (Max) (1) W/W 5,79
SEER/ηsc (2) % 7,7 A++
Pdesign (cooling) kW 7,1
Input power cooling (Nominal) kW 1,75
Input power cooling (Min) kW 0,38
Input power cooling (Max) kW 3,35
Annual energy consumption cooling (3) kWh/a 323
Heating capacity (Nominal) kW 8,0
Heating capacity (Min) kW 2,0
Heating capacity (Max) kW 9,0
COP (Nominal) (1) W/W 4,30
COP (Min) (1) W/W 3,16
COP (Max) (1) W/W 5,56
SCOP/ηsc (2) % 4,8 A++
Pdesign at -10°C kW 5,2
Input power heating (Nominal) kW 1,86
Input power heating (Min) kW 0,36
Input power heating (Max) kW 2,85
Annual energy consumption heating (3) kWh/a 1.517
Indoor unit S-6071PU3E
Indoor air flow (Hi) m³/min 22,0
Indoor air flow (Med) m³/min 16,0
Indoor air flow (Lo) m³/min 13,0
Moisture removal volume L/h 2,5
Indoor sound pressure (Med) (4) dB(A) 31
Indoor sound pressure (Lo) (4) dB(A) 28
Indoor sound power (Hi) dB(A) 52
Indoor sound power (Med) dB(A) 46
Indoor sound power (Lo) dB(A) 43
Indoor dimension (Height) mm 256
Indoor dimension (Width) mm 840
Indoor dimension (Depth) mm 840
Panel dimension (Height) mm 33,5
Panel dimension (Depth) mm 950
Indoor net weight kg 20
Panel net weight kg 5
nanoe X Generator Mark 1
Outdoor unit U-71PZH4E5
Outdoor power source V 220 - 230 - 240
Current in cooling (1p 220V / 3p 380) A 8,85
Current in cooling (1p 230V / 3p 400) A 8,45
Current in cooling (1p 240V / 3p 415) A 8,10
Current in heating (1p 220V / 3p 380) A 9,40
Current in heating (1p 230V / 3p 400) A 9,00
Current in heating (1p 240V / 3p 415) A 8,60
Outdoor air flow (Cool) m³/min 62,0
Outdoor air flow (Heat) m³/min 66,0
Outdoor sound pressure (Cool -Hi) dB(A) 48
Outdoor sound pressure (Heat -Hi) dB(A) 50
Outdoor sound power (Cool -Hi) dB(A) 65
Outdoor sound power (Heat -Hi) dB(A) 67
Outdoor dimension (Height) mm 996
Outdoor dimension (Width) mm 980
Outdoor dimension (Depth) mm 370
Outdoor net weight kg 66
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88)
Pipe length range m 5 ~ 60
Elevation difference (in/out) (7) m 15 / 30
Pipe length for additional gas m 30
Additional gas amount g/m 30
Refrigerant (R32) / CO2 Eq. kg / T 1,95 / 1,32
Operating range (Cool - Min) °C -15
Operating range (Cool - Max) °C +52
Operating range (Heat - Min) °C -20
Operating range (Heat - Max) °C +24

1) EER and COP calculation is based in accordance to EN14511.
2) For models below 12kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12kW, the ηs,c / ηs,h values is calculated based on EN 14825.
3) Factory setting.
4) The sound pressure of the units shows the value measured of the position 1,5m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
5) Connect the liquid socket tube (Ø6,35-Ø9,52) to the liquid tubing side indoor unit.
6) Connect the gas socket tube (Ø12,70-Ø15,88) to the gas tubing side indoor unit.
7) Outdoor unit located lower / outdoor unit located higher.
8) Pipe length up to 30m.

* Recommended fuse for the indoor 3A.
** Above values are in the case of nanoe™ X OFF.