PACi Standard 4 Way 90x90 Cassette - PU3 - R32

Previous capacity Next capacity

New 4 way 90x90 cassette - PU3 for R32 PACi

Powerful turbo fan and intelligent Econavi sensor ensures high energy efficiency and nanoe™ X which is equipped as standard provides an exceptional level of indoor air quality.


Bringing nature’s balance indoors

Specifications

See all
PACi Standard 4 Way 90x90 Cassette - PU3 - R32
7.1 kW
Kit KIT-71PU3Z25
Remote controller CZ-RTC6
Cooling capacity (Nominal) kW 7,1
Cooling capacity (Min) kW 2,0
Cooling capacity (Max) kW 7,7
EER (Nominal) (1) W/W 3,50
EER (Min) (1) W/W 8,00
EER (Max) (1) W/W 3,01
SEER/ηsc (2) % 7,6 A++
Pdesign (cooling) kW 7,1
Input power cooling (Nominal) kW 2,03
Input power cooling (Min) kW 0,25
Input power cooling (Max) kW 2,56
Annual energy consumption cooling (3) kWh/a 327
Heating capacity (Nominal) kW 7,1
Heating capacity (Min) kW 1,8
Heating capacity (Max) kW 8,1
COP (Nominal) (1) W/W 4,36
COP (Min) (1) W/W 9,47
COP (Max) (1) W/W 3,80
SCOP/ηsc (2) % 4,7 A++
Pdesign at -10°C kW 6,0
Input power heating (Nominal) kW 1,63
Input power heating (Min) kW 0,19
Input power heating (Max) kW 2,13
Annual energy consumption heating (3) kWh/a 1787
Indoor unit S-6071PU3E
Indoor air flow (Hi) m³/min 22,0
Indoor air flow (Med) m³/min 16,0
Indoor air flow (Lo) m³/min 13,0
Moisture removal volume L/h 2,5
Indoor sound pressure (Med) (4) dB(A) 31
Indoor sound pressure (Lo) (4) dB(A) 28
Indoor sound power (Hi) dB(A) 52
Indoor sound power (Med) dB(A) 46
Indoor sound power (Lo) dB(A) 43
Indoor dimension (Height) mm 256
Indoor dimension (Width) mm 840
Indoor dimension (Depth) mm 840
Panel dimension (Height) mm 33,5
Panel dimension (Depth) mm 950
Indoor net weight kg 20
Panel net weight kg 5
nanoe X Generator mar-01
Outdoor unit U-71PZ2E5
Outdoor power source V 220 - 230 - 240
Current in cooling (1p 220V / 3p 380) A 9,95
Current in cooling (1p 230V / 3p 400) A 9,50
Current in cooling (1p 240V / 3p 415) A 9,10
Current in heating (1p 220V / 3p 380) A 8,05
Current in heating (1p 230V / 3p 400) A 7,70
Current in heating (1p 240V / 3p 415) A 7,35
Outdoor air flow (Cool) m³/min 50
Outdoor air flow (Heat) m³/min 45
Outdoor sound pressure (Cool -Hi) dB(A) 49
Outdoor sound pressure (Heat -Hi) dB(A) 49
Outdoor sound power (Cool -Hi) dB(A) 69
Outdoor sound power (Heat -Hi) dB(A) 69
Outdoor dimension (Height) mm 695
Outdoor dimension (Width) mm 875
Outdoor dimension (Depth) mm 320
Outdoor net weight kg 44
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88)
Pipe length range m 3 ~ 40
Elevation difference (in/out) (5) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 35
Refrigerant (R32) / CO2 Eq. kg / T 1,45 / 0,979
Operating range (Cool - Min) °C -10
Operating range (Cool - Max) °C +43
Operating range (Heat - Min) °C -15
Operating range (Heat - Max) °C +24
(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12kW, the ηsc / ηsh values is calculated based on EN 14825.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) The sound pressure of the units shows the value measured of the position 1,5m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(5) When installing the outdoor unit at a higher position than the indoor unit.
* Recommended fuse for the indoor 3A.
** Above values are in the case of nanoe™ X OFF.

Complementary products