PACi NX Series Standard wall-mounted Inverter+ - R32
The wall-mounted units with stylish matt colour can be offered for many applications such as studios, gyms, high ceiling areas and even computer server rooms.
The compact design and flat face ensure discreet installation, even in a small space.
- Modern design with a flat face and compact size
- DC fan for better efficiency and control
- Six directional piping outlet
- nanoe™ X (Generator Mark 2= 9,6 trillion hydroxyl radicals/sec) as standard for better indoor air quality
- Wired remote control CZ-RTC6BL allows easy system setting via Bluetooth®
- Easy connection and control of external fan or ERV using the connector PAW-FDC on the indoor unit PCB. The external device can be controlled by the remote control of the Panasonic indoor unit
The next generation of commercial air conditioners is here
Specifications
PACi NX Series Standard wall-mounted Inverter+ - R32 | |||
---|---|---|---|
3.6 kW | |||
Kit | KIT-36PK3Z5 | ||
Remote controller | CZ-RTC5B | ||
Cooling capacity (Nominal) | kW | 3,6 | |
Cooling capacity (Min) | kW | 1,5 | |
Cooling capacity (Max) | kW | 4,0 | |
EER (Nominal) (1) | W/W | 4,14 | |
SEER (2) | 7,6 A++ | ||
Pdesign (cooling) | kW | 3,6 | |
Input power cooling (Nominal) | kW | 0,87 | |
Annual energy consumption cooling (3) | kWh/a | 166 | |
Heating capacity (Nominal) | kW | 3,6 | |
Heating capacity (Min) | kW | 1,5 | |
Heating capacity (Max) | kW | 4,6 | |
COP (Nominal) (1) | W/W | 4,62 | |
SCOP (2) | 4,5 A+ | ||
Pdesign at -10°C | kW | 2,8 | |
Input power heating (Nominal) | kW | 0,78 | |
Annual energy consumption heating (3) | kWh/a | 872 | |
Indoor unit | S-3650PK3E | ||
Indoor air flow (Hi) | m³/min | 13,0 | |
Indoor air flow (Med) | m³/min | 11,0 | |
Indoor air flow (Lo) | m³/min | 9,0 | |
Moisture removal volume | L/h | 0,9 | |
Indoor sound pressure (Med) (4) | dB(A) | 31 | |
Indoor sound pressure (Lo) (4) | dB(A) | 27 | |
Indoor sound power (Hi) | dB(A) | 51 | |
Indoor sound power (Med) | dB(A) | 47 | |
Indoor sound power (Lo) | dB(A) | 43 | |
Indoor dimension (Height) | mm | 302 | |
Indoor dimension (Width) | mm | 1.120 | |
Indoor dimension (Depth) | mm | 236 | |
Indoor net weight | kg | 13 | |
nanoe X Generator | Mark 2 | ||
Outdoor unit | U-36PZ3E5 | ||
Outdoor power source | V | 220 - 230 - 240 | |
Current in cooling (1p 220V / 3p 380) | A | 4,05 | |
Current in cooling (1p 230V / 3p 400) | A | 3,85 | |
Current in cooling (1p 240V / 3p 415) | A | 3,70 | |
Current in heating (1p 220V / 3p 380) | A | 3,65 | |
Current in heating (1p 230V / 3p 400) | A | 3,50 | |
Current in heating (1p 240V / 3p 415) | A | 3,35 | |
Outdoor air flow (Cool) | m³/min | 33,6 | |
Outdoor air flow (Heat) | m³/min | 34,0 | |
Outdoor sound pressure (Cool -Hi) | dB(A) | 46 | |
Outdoor sound pressure (Heat -Hi) | dB(A) | 47 | |
Outdoor sound power (Cool -Hi) | dB(A) | 64 | |
Outdoor sound power (Heat -Hi) | dB(A) | 66 | |
Outdoor dimension (Height) | mm | 619 | |
Outdoor dimension (Width) | mm | 824 | |
Outdoor dimension (Depth) | mm | 299 | |
Outdoor net weight | kg | 32 | |
Pipe diameter (Liquid) | Inch (mm) | 1/4 (6,35) | |
Pipe diameter (Gas) | Inch (mm) | 1/2 (12,70) | |
Pipe length range | m | 3 ~ 15 | |
Elevation difference (in/out) (7) | m | 15 / 15 (8) | |
Pipe length for additional gas | m | 7,5 | |
Additional gas amount | g/m | 10 | |
Refrigerant (R32) / CO2 Eq. | kg / T | 0,87 / 0,59 | |
Operating range (Cool - Min) | °C | -10 | |
Operating range (Cool - Max) | °C | +43 | |
Operating range (Heat - Min) | °C | -15 | |
Operating range (Heat - Max) | °C | +24 |
1) EER and COP calculation is based in accordance with EN14511.
2) For models below 12kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12kW, the ηsc / ηsh values are calculated based on EN 14825.
3) Factory setting.
4) The sound pressure of the units shows the value measured of the position 1m in front of the main body and 1m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
5) Connect the liquid socket tube (Ø6,35-Ø9,52) to the liquid tubing side indoor unit.
6) Connect the gas socket tube (Ø12,70-Ø15,88) to the gas tubing side indoor unit.
7) When installing the outdoor unit at a higher position than the indoor unit.
8) Outdoor unit located lower / outdoor unit located higher.
* Recommended fuse for the indoor 3A.
** Above values are in the case of nanoe™ X OFF.