PACi Elite High Static Pressure Hide Away • R32
The ducted systems are the ideal solution for flexible, concealed air conditioning and the optional 200mm spigots ensure simple, hassle-free connection to spiral ductwork.
- High ESP (external static pressure) up to 150 Pa
- Automatic learning function for the required static pressure on site during commissioning (a standard wired remote controller is required)
- DC FAN for better efficiency and control
- Built in drain pump
- Datanavi simple support tool App with remote controller (CZ-RTC5B)
- Twin split options
- Easy connection and control of external fan or ERV using the connector PAW-FDC on the indoor unit PCB. The external device can be controlled by the remote control of the Panasonic indoor unit
Specifications
PACi Elite High Static Pressure Hide Away • R32 | |||
---|---|---|---|
3.6 kW | |||
EER (Nominal) (1) | W/W | 4,74 | |
COP (Nominal) (1) | W/W | 4,76 | |
Refrigerant (R32) / CO2 Eq. | kg / T | — | |
EER (Nominal) (1) | W/W | 4,74 | |
COP (Nominal) (1) | W/W | 4,76 | |
External static pressure (Nominal) (4) | Pa | 70 | |
External static pressure (Min) (4) | Pa | 10 | |
External static pressure (Max) (4) | Pa | 150 | |
Indoor sound pressure (Hi) (5) | dB(A) | 33 | |
Indoor sound pressure (Med) (5) | dB(A) | 29 | |
Indoor sound pressure (Lo) (5) | dB(A) | 25 | |
Elevation difference (in/out) (6) | m | 30 | |
Refrigerant (R32) / CO2 Eq. | kg / T | — |
(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the SEER and SCOP is calculated based on values of EU/2281/2016.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) Medium External static pressure setting from factory.
(5) The sound pressure of the units shows the value measured of the position 1,5 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(6) When installing the outdoor unit at a higher position than the indoor unit.
(7) For models 100 ~ 140PZH2E5(8), it is possible to operate the lowest -20 °C in the computer rooms with the piping length of 30 m or less.
* Recommended fuse for the indoor 3 A.