Big PACi NX high static pressure hide-away 20,0-25,0kW · R32
The PAC NX Elite range has been expanded to include the Big PACi NX models 20,0‑25,0 kW.
· Highly efficient with compact indoor body
· Split-able Hide Away indoor design for easy & flexible piping work
· nanoe™ X (Generator Mark 3 = 48 trillion hydroxyl radicals/sec) as standard
· The compact outdoor unit with one fan will fit in limited installation space
· Long piping allowance maximum 100m
· Extended operation range up to 52°C in cooling and down to -20°C in heating
· Demand response compliant as a standard function
Specifications
Big PACi NX high static pressure hide-away 20,0-25,0kW · R32 | |||
---|---|---|---|
20.0 kW | |||
Kit | KIT-200PE4ZH8 | ||
Remote controller | CZ-RTC5B | ||
Cooling capacity (Nominal) | kW | 19,0 | |
Cooling capacity (Min) | kW | 5,7 | |
Cooling capacity (Max) | kW | 20,0 | |
EER (Nominal) (1) | W/W | 3,20 | |
EER (Min) (1) | W/W | 2,78 | |
EER (Max) (1) | W/W | 4,60 | |
SEER/ηsc (2) | % | 237,8% | |
Pdesign (cooling) | kW | 19,0 | |
Input power cooling (Nominal) | kW | 5,93 | |
Input power cooling (Min) | kW | 1,24 | |
Input power cooling (Max) | kW | 7,20 | |
Heating capacity (Nominal) | kW | 22,4 | |
Heating capacity (Min) | kW | 5,0 | |
Heating capacity (Max) | kW | 24,5 | |
COP (Nominal) (1) | W/W | 3,55 | |
COP (Min) (1) | W/W | 3,27 | |
COP (Max) (1) | W/W | 4,76 | |
SCOP/ηsc (2) | % | 146,0% | |
Pdesign at -10°C | kW | 16,0 | |
Input power heating (Nominal) | kW | 6,31 | |
Input power heating (Min) | kW | 1,05 | |
Input power heating (Max) | kW | 7,50 | |
Indoor unit | S-200PE4E | ||
External static pressure at shipment (adjustable) | Pa | 75 (3) (120 / 180) | |
Air flow (Hi) | m³/min | 72 | |
Air flow (Med) | m³/min | 63 | |
Air flow (Lo) | m³/min | 53 | |
Indoor sound pressure (Med) (4) | dB(A) | 44 | |
Indoor sound pressure (Lo) (4) | dB(A) | 41 | |
Indoor dimension (Height) | mm | 486 | |
Indoor dimension (Width) | mm | 1456 | |
Indoor dimension (Depth) | mm | 916 | |
Indoor net weight | kg | 83 | |
Outdoor unit | U-200PZH4E8 | ||
Outdoor recommended fuse | A | 30 | |
Outdoor air flow (Cool) | m³/min | 116 | |
Outdoor air flow (Heat) | m³/min | 136 | |
Outdoor sound pressure (Cool -Hi) | dB(A) | 57 | |
Outdoor sound pressure (Heat -Hi) | dB(A) | 61 | |
Outdoor sound power (Cool -Hi) | dB(A) | 76 | |
Outdoor sound power (Heat -Hi) | dB(A) | 80 | |
Outdoor dimension (Height) (5) | mm | 996 | |
Outdoor dimension (Width) (5) | mm | 1 140 | |
Outdoor dimension (Depth) (5) | mm | 460 | |
Outdoor net weight | kg | 109 | |
Pipe diameter (Liquid) | Inch (mm) | 1/2 (12,7) | |
Pipe diameter (Gas) | Inch (mm) | 7/8 (22,22) | |
Pipe length range | m | 5 ~ 100 | |
Elevation difference (in/out) | m | 30 | |
Pipe length for additional gas | m | 30 | |
Additional gas amount | g/m | 80 | |
Refrigerant (R32) / CO2 Eq. | kg / T | 4,8 / 3,24 | |
Operating range (Cool - Min) | °C | -15 | |
Operating range (Cool - Max) | °C | +52 | |
Operating range (Heat - Min) | °C | -20 | |
Operating range (Heat - Max) | °C | +35 |
1) EER and COP calculation is based in accordance to EN14511.
2) For models above 12kW, the ηs,c / ηs,h values is calculated based on EN 14825.
3) Factory setting.
4) The sound pressure of the units shows the value measured of the position 1,5m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
5) Add 100mm for indoor unit or 70mm for outdoor unit for piping port.