PACi NX Series Standard 4 way 90x90 cassette Inverter+ - R32
4 way 90x90 cassette - PU3
Powerful turbo fan and intelligent Econavi sensor ensure high energy efficiency, and nanoe™ X which is equipped as standard provides an exceptional level of indoor air quality.
- High performance turbo fan, path system for heat exchanger
- Econavi: An optional intelligent sensor to reduce waste of energy
- nanoe™ X (Generator Mark 1= 4,8 trillion OH radicals/ sec) as standard for better indoor air quality, indoor unit internal cleaning with nanoe™ X and dry operation
- Lower noise in slow fan operation
- Light weight, easy piping and integrated drain pump for quick installation
- New wired remote control CZ-RTC6BL allows easy system setting via Bluetooth®
- High volume fresh air input with the optional air-intake chamber (CZ-FDU3+CZ-ATU2)
The next generation of commercial air conditioners is here
Specifications
PACi NX Series Standard 4 way 90x90 cassette Inverter+ - R32 | |||
---|---|---|---|
14.0 kW | |||
Kit | KIT-140PU3Z8 | ||
Remote controller | CZ-RTC5B | ||
Cooling capacity (Nominal) | kW | 14,0 | |
Cooling capacity (Min) | kW | 3,3 | |
Cooling capacity (Max) | kW | 15,0 | |
EER (Nominal) (1) | W/W | 3,23 | |
EER (Min) (1) | W/W | 5,32 | |
EER (Max) (1) | W/W | 2,73 | |
SEER/ηsc (2) | % | 256,5 % | |
Pdesign (cooling) | kW | 14,0 | |
Input power cooling (Nominal) | kW | 4,34 | |
Input power cooling (Min) | kW | 0,62 | |
Input power cooling (Max) | kW | 5,50 | |
Annual energy consumption cooling (3) | kWh/a | — | |
Heating capacity (Nominal) | kW | 14,0 | |
Heating capacity (Min) | kW | 3,4 | |
Heating capacity (Max) | kW | 16,0 | |
COP (Nominal) (1) | W/W | 4,18 | |
COP (Min) (1) | W/W | 5,48 | |
COP (Max) (1) | W/W | 3,33 | |
SCOP/ηsc (2) | % | 152,4 % | |
Pdesign at -10°C | kW | 14,0 (at -7 °C) | |
Input power heating (Nominal) | kW | 3,35 | |
Input power heating (Min) | kW | 0,62 | |
Input power heating (Max) | kW | 4,80 | |
Annual energy consumption heating (3) | kWh/a | — | |
Indoor unit | S-1014PU3E | ||
Indoor air flow (Hi) | m³/min | 38,0 | |
Indoor air flow (Med) | m³/min | 29,0 | |
Indoor air flow (Lo) | m³/min | 20,0 | |
Moisture removal volume | L/h | 6,0 | |
Indoor sound pressure (Med) (4) | dB(A) | 40 | |
Indoor sound pressure (Lo) (4) | dB(A) | 34 | |
Indoor sound power (Hi) | dB(A) | 62 | |
Indoor sound power (Med) | dB(A) | 55 | |
Indoor sound power (Lo) | dB(A) | 49 | |
Indoor dimension (Height) | mm | 319 | |
Indoor dimension (Width) | mm | 840 | |
Indoor dimension (Depth) | mm | 840 | |
Panel dimension (Height) | mm | 33,5 | |
Panel dimension (Depth) | mm | 950 | |
Indoor net weight | kg | 25 | |
Panel net weight | kg | 5 | |
nanoe X Generator | Mark 1 | ||
Outdoor unit | U-140PZ3E8 | ||
Outdoor power source | V | 380 - 400 - 415 | |
Current in cooling (1p 220V / 3p 380) | A | 7,00 | |
Current in cooling (1p 230V / 3p 400) | A | 6,65 | |
Current in cooling (1p 240V / 3p 415) | A | 6,40 | |
Current in heating (1p 220V / 3p 380) | A | 5,40 | |
Current in heating (1p 230V / 3p 400) | A | 5,15 | |
Current in heating (1p 240V / 3p 415) | A | 4,95 | |
Outdoor air flow (Cool) | m³/min | 84,0 | |
Outdoor air flow (Heat) | m³/min | 82,0 | |
Outdoor sound pressure (Cool -Hi) | dB(A) | 56 | |
Outdoor sound pressure (Heat -Hi) | dB(A) | 56 | |
Outdoor sound power (Cool -Hi) | dB(A) | 74 | |
Outdoor sound power (Heat -Hi) | dB(A) | 74 | |
Outdoor dimension (Height) | mm | 996 | |
Outdoor dimension (Width) | mm | 980 | |
Outdoor dimension (Depth) | mm | 370 | |
Outdoor net weight | kg | 87 | |
Pipe diameter (Liquid) | Inch (mm) | 3/8 (9,52) | |
Pipe diameter (Gas) | Inch (mm) | 5/8 (15,88) | |
Pipe length range | m | 5 ~ 50 | |
Elevation difference (in/out) (7) | m | 15 / 30 (8) | |
Pipe length for additional gas | m | 30 | |
Additional gas amount | g/m | 45 | |
Refrigerant (R32) / CO2 Eq. | kg / T | 2,80 / 1,89 | |
Operating range (Cool - Min) | °C | -10 | |
Operating range (Cool - Max) | °C | +43 | |
Operating range (Heat - Min) | °C | -15 | |
Operating range (Heat - Max) | °C | +24 |
1) EER and COP calculation is based in accordance with EN14511.
2) For models below 12kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12kW, the ηsc / ηsh values are calculated based on EN 14825.
3) Factory setting.
4) The sound pressure of the units shows the value measured of the position 1,5m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
5) Connect the liquid socket tube (Ø6,35-Ø9,52) to the liquid tubing side indoor unit.
6) Connect the gas socket tube (Ø12,70-Ø15,88) to the gas tubing side indoor unit.
7) When installing the outdoor unit at a higher position than the indoor unit.
8) Outdoor unit located lower / outdoor unit located higher.
* Recommended fuse for the indoor 3A.
** Above values are in the case of nanoe™ X OFF.