NX Series Jet Air Stream
PACi NX Jet Air Stream
Energy-saving solution for year-round heating and cooling in large and high
· High air volume up to 5000m³/h
· Long maximum air throw distance of 30m
Optimal comfort with Smart Jet - self-directing nozzles
· Precise temperature control
· Preventing stratification and maintaining an ideal temperature exclusively in the occupied area
Specifications
NX Series Jet Air Stream | |||
---|---|---|---|
14.0 kW | |||
Kit | KIT-140MC5ZH5 | ||
Remote controller | PCZ-AHRX0012 | ||
Cooling capacity (Nominal) | kW | 13,4 | |
Cooling capacity (Min) | kW | 3,3 | |
Cooling capacity (Max) | kW | 15,3 | |
EER (Nominal) (1) | W/W | 3,38 | |
EER (Min) (1) | W/W | 2,59 | |
EER (Max) (1) | W/W | 4,18 | |
Heating capacity (Nominal) | kW | 15,3 | |
Heating capacity (Min) | kW | 3,3 | |
Heating capacity (Max) | kW | 17,4 | |
COP (Nominal) (1) | W/W | 3,33 | |
COP (Min) (1) | W/W | 3,10 | |
COP (Max) (1) | W/W | 4,29 | |
Indoor unit | P-VTVF140MC5-PE | ||
Indoor dimension (Height) | mm | 802 | |
Indoor dimension (Width) | mm | 1.010 | |
Indoor dimension (Depth) | mm | 893 | |
Indoor net weight | kg | 75 | |
Outdoor unit | U-140PZH4E5 | ||
Outdoor sound pressure (Cool -Hi) | dB(A) | 56 | |
Outdoor sound pressure (Heat -Hi) | dB(A) | 56 | |
Outdoor dimension (Height) | mm | 996 | |
Outdoor dimension (Width) | mm | 980 | |
Outdoor dimension (Depth) | mm | 370 | |
Outdoor net weight | kg | 86 | |
Pipe diameter (Liquid) | Inch (mm) | 3/8 (9,52) | |
Pipe diameter (Gas) | Inch (mm) | 5/8 (15,88) | |
Pipe length range | m | 5 ~ 100 | |
Elevation difference (in/out) | m | 15 / 30 (4) | |
Pipe length for additional gas | m | 30 | |
Additional gas amount | g/m | 40 | |
Refrigerant (R32) / CO2 Eq. | kg / T | 3,00 / 2,03 | |
Operating range (Cool - Min) | °C | -20 (5) | |
Operating range (Cool - Max) | °C | +52 | |
Operating range (Heat - Min) | °C | -20 | |
Operating range (Heat - Max) | °C | +24 |
1) EER and COP calculation is based in accordance to EN 14511.
2) Average sound pressure at 5m Lp.
3) Radiated sound power at 5m Lp.
4) Outdoor unit located lower / outdoor unit located higher.
5) Pipe length up to 30m.