PACi NX Series Elite adaptive ducted unit Inverter+ - R32

Design duct range PF3

2 installation possibilities (horizontal / vertical) with high ESP 150Pa allows flexible installation.

* The performance of nanoe™ X air can be expected even by 10m long duct by Panasonic internal survey.

The next generation of commercial air conditioners is here

New adaptive ducted PF3

The next generation of commercial air conditioners is here

Specifications

See all
PACi NX Series Elite adaptive ducted unit Inverter+ - R32
12.5 kW
Kit KIT-125PF3ZH45
Remote controller CZ-RTC5B
Cooling capacity (Nominal) kW 12,1
Cooling capacity (Min) kW 3,2
Cooling capacity (Max) kW 13,6
EER (Nominal) (1) W/W 3,53
EER (Min) (1) W/W 3,00
EER (Max) (1) W/W 5,00
SEER/ηsc (2) % 281,7%
Pdesign (cooling) kW 12,1
Input power cooling (Nominal) kW 3,43
Input power cooling (Min) kW 0,64
Input power cooling (Max) kW 4,54
Annual energy consumption cooling (3) kWh/a
Heating capacity (Nominal) kW 13,5
Heating capacity (Min) kW 3,2
Heating capacity (Max) kW 15,4
COP (Nominal) (1) W/W 3,46
COP (Min) (1) W/W 3,06
COP (Max) (1) W/W 5,16
SCOP/ηsc (2) % 165,0%
Pdesign at -10°C kW 9,3
Input power heating (Nominal) kW 3,90
Input power heating (Min) kW 0,62
Input power heating (Max) kW 5,04
Annual energy consumption heating (3) kWh/a
Indoor unit S-1014PF3E
External static pressure (Nominal) (4) Pa 50
External static pressure (Min) (4) Pa 10
External static pressure (Max) (4) Pa 150
Moisture removal volume L/h 34,0
Indoor air flow (Hi) m³/min 29,0
Indoor air flow (Med) m³/min 23,0
Indoor air flow (Lo) m³/min 4,1
Indoor sound pressure (Hi) (5) dB(A) 35
Indoor sound pressure (Med) (5) dB(A) 31
Indoor sound pressure (Lo) (5) dB(A) 27
Indoor sound power (Hi) dB(A) 58
Indoor sound power (Med) dB(A) 54
Indoor sound power (Lo) dB(A) 50
Indoor dimension (Height) mm 250
Indoor dimension (Width) mm 1.400
Indoor dimension (Depth) mm 730
Indoor net weight kg 39
nanoe X Generator Mark 2
Outdoor unit U-125PZH4E5
Outdoor power source V 220 - 230 - 240
Current in cooling (1p 220V / 3p 380) A 16,80
Current in cooling (1p 230V / 3p 400) A 16,00
Current in cooling (1p 240V / 3p 415) A 15,40
Current in heating (1p 220V / 3p 380) A 19,10
Current in heating (1p 230V / 3p 400) A 18,20
Current in heating (1p 240V / 3p 415) A 17,50
Outdoor air flow (Cool) m³/min 86,0
Outdoor air flow (Heat) m³/min 78,0
Outdoor sound pressure (Cool -Hi) dB(A) 55
Outdoor sound pressure (Heat -Hi) dB(A) 55
Outdoor sound power (Cool -Hi) dB(A) 73
Outdoor sound power (Heat -Hi) dB(A) 73
Outdoor dimension (Height) mm 996
Outdoor dimension (Width) mm 980
Outdoor dimension (Depth) mm 370
Outdoor net weight kg 86
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88)
Pipe length range m 5 ~ 100
Elevation difference (in/out) (8) m 15 / 30
Pipe length for additional gas m 30
Additional gas amount g/m 40
Refrigerant (R32) / CO2 Eq. kg / T 3,00 / 2,03
Operating range (Cool - Min) °C -20 (9)
Operating range (Cool - Max) °C +52
Operating range (Heat - Min) °C -20
Operating range (Heat - Max) °C +24

1) EER and COP calculation is based in accordance to EN14511.
2) For models below 12kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12kW, the ηs,c / ηs,h values is calculated based on EN 14825.
3) Factory setting.
4) Medium external static pressure setting from factory.
5) The sound pressure of the units shows the value measured of the position 1,5m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
6) Connect the liquid socket tube (Ø6,35-Ø9,52) to the liquid tubing side indoor unit.
7) Connect the gas socket tube (Ø12,70-Ø15,88) to the gas tubing side indoor unit. 8) Outdoor unit located lower / outdoor unit located higher.
9) Pipe length up to 30m.
* Recommended fuse for the indoor 3A.

** Above values are in the case of standard installation(horizontal installation in the celling, rear side air intake) and nanoe™ X OFF.