Advanced ERV ZY Series
Advanced energy recovery ventilation ZY Series
- Recovers up to 83% of the heat in the outgoing air
- 9 model line-up including 2.000m³/h model
- DC motors
- ESP up to 150Pa
- An effective F7 grade filter built-in as a standard
- Intuitive remote controller with RS485 connection
Best efficiency ECOi Series
Specifications
Advanced ERV ZY Series | |||
---|---|---|---|
650 m³/h | |||
Indoor unit | FV-65ZY1G (1) | ||
Power supply (Voltage) | V | 220 - 240 | |
Power supply (Phase) | 1φ | ||
Power supply (Frequency) | Hz | 50 | |
Motor type | DC | ||
ERV - Air flow (Max) | m³/h | 650 | |
ERV - External static pressure (Max) | Pa | 150 | |
ERV - Sound power (Max) (2) | dB(A) | 45 | |
ERV - Input power (Max) | W | 420 ~ 462 | |
Heat exchange efficiency - Cooling (Max) (3) | % | 64,0 | |
Heat exchange efficiency - Heating (Max) (3) | % | 82,0 | |
Enthalpy exchange efficiency - Cooling (Max) | % | 62,5 | |
Enthalpy exchange efficiency - Heating (Max) | % | 72,0 | |
Adapter diameter | mm | 200 | |
Dimension (Height) | mm | 404 | |
Dimension (Width) | mm | 954 | |
Dimension (Depth) | mm | 1.008 | |
Net weight | kg | 48 |
(1) Different dimensions depending on models.
(2) Measurement of noise 1,5m below the center of the main unit (anechoic chamber).
(3) Heat exchange efficiency measurement standard JIS B 8628 (2003).
* JIS B 8628 (2017) is used in the measurement environment.