PACi Standard Ceiling • R32

This range of ceiling mounted units feature a DC fan motor for increased efficiency and reduced operating sound levels.

All the units are the same height and depth for a uniform appearance in mixed installations. A knock out is provided to allow for supplementary fresh air for improved air quality.

Specifications

See all
PACi Standard Ceiling • R32
10.0 kW
Kit KIT-100PT2Z5
Remote controller CZ-RTC5B
EER (Min) (1) W/W 5,36
EER (Max) (1) W/W 2,80
Annual energy consumption cooling (3) kWh/a 535
Annual energy consumption cooling (3) kWh/a 535
COP (Min) (1) W/W 5,36
COP (Max) (1) W/W 3,50
Annual energy consumption heating (3) kWh/a 3324
Indoor air flow (Hi) m³/min 30,0
Indoor air flow (Med) m³/min 25,0
Indoor air flow (Lo) m³/min 23,0
Moisture removal volume L/h 6,0
Indoor sound pressure (Med) (4) dB(A) 37
Indoor sound pressure (Lo) (4) dB(A) 35
Indoor sound power (Hi) dB(A) 60
Indoor sound power (Med) dB(A) 55
Indoor sound power (Lo) dB(A) 53
Outdoor unit U-100PZ2E5
Outdoor power source V 220 - 230 - 240
Current in cooling (1p 220V / 3p 380) A 12,80
Current in cooling (1p 230V / 3p 400) A 12,20
Current in cooling (1p 240V / 3p 415) A 11,70
Current in heating (1p 220V / 3p 380) A 10,90
Current in heating (1p 230V / 3p 400) A 10,40
Current in heating (1p 240V / 3p 415) A 10,00
Outdoor air flow (Cool) m³/min 76
Outdoor air flow (Heat) m³/min 70
Outdoor sound pressure (Cool -Hi) dB(A) 52
Outdoor sound pressure (Heat -Hi) dB(A) 52
Outdoor sound power (Cool -Hi) dB(A) 70
Outdoor sound power (Heat -Hi) dB(A) 70
Outdoor dimension (Height) mm 996
Outdoor dimension (Width) mm 980
Outdoor dimension (Depth) mm 370
Pipe length range m 5 ~ 50
Elevation difference (in/out) (5) m 30

(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the SEER and SCOP is calculated based on values of EU/2281/2016.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) The sound pressure of the units shows the value measured of the position 1 m in front of the main body and 1 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(5) When installing the outdoor unit at a higher position than the indoor unit.
* Recommended fuse for the indoor 3 A.

Complementary products