PACi Elite loft • R32

Tidligere egenskab Næste kapacitet

Loftsmonterede enheder spreder luften langt og bredt, hvilket er godt i store rum. Højden og dybden er den samme for alle kapaciteter, så enhederne ser ens ud i blandede installationer.

Specifikationer

Se alle
PACi Elite loft • R32
3.6 kW
Kit KIT-36PT2ZH5
Remote controller CZ-RTC5B
Cooling capacity (Nominal) kW 3,6
Cooling capacity (Min) kW 1,5
Cooling capacity (Max) kW 4,0
EER (Nominal) (1) W/W 5,07
SEER (2) 7,2 A++
Pdesign (cooling) kW 3,6
Input power cooling (Nominal) kW 0,71
Annual energy consumption cooling (3) kWh/a 175
Annual energy consumption cooling (3) kWh/a 175
Heating capacity (Nominal) kW 4,0
Heating capacity (Min) kW 1,5
Heating capacity (Max) kW 5,0
COP (Nominal) (1) W/W 5,19
SCOP (2) 4,8 A++
Pdesign at -10°C kW 3,6
Input power heating (Nominal) kW 0,77
Annual energy consumption heating (3) kWh/a 1050
Indoor unit S-36PT2E5B
Indoor air flow (Hi) m³/min 14,0
Indoor air flow (Med) m³/min 12,0
Indoor air flow (Lo) m³/min 10,5
Indoor sound pressure (Med) (4) dB(A) 32
Indoor sound pressure (Lo) (4) dB(A) 29
Indoor dimension (Height) mm 235
Indoor dimension (Width) mm 960
Indoor dimension (Depth) mm 690
Indoor net weight kg 27
Outdoor unit U-36PZH2E5
Outdoor power source V 220 - 230 - 240
Current in cooling (1p 220V / 3p 380) A 3,35
Current in cooling (1p 230V / 3p 400) A 3,25
Current in cooling (1p 240V / 3p 415) A 3,10
Current in heating (1p 220V / 3p 380) A 3,65
Current in heating (1p 230V / 3p 400) A 3,50
Current in heating (1p 240V / 3p 415) A 3,35
Outdoor air flow (Cool) m³/min 40
Outdoor air flow (Heat) m³/min 40
Outdoor sound pressure (Cool -Hi) dB(A) 43
Outdoor sound pressure (Heat -Hi) dB(A) 44
Outdoor sound power (Cool -Hi) dB(A) 62
Outdoor sound power (Heat -Hi) dB(A) 64
Outdoor dimension (Height) mm 695
Outdoor dimension (Width) mm 875
Outdoor dimension (Depth) mm 320
Outdoor net weight kg 43
Pipe diameter (Liquid) Inch (mm) 1/4 (6,35)
Pipe diameter (Gas) Inch (mm) 1/2 (12,70)
Pipe length range m 3 ~ 40
Elevation difference (in/out) (5) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 20
Refrigerant (R32) / CO2 Eq. kg / T 1,15 / 0,776
Operating range (Cool - Min) °C -15
Operating range (Cool - Max) °C 46
Operating range (Heat - Min) °C -20
Operating range (Heat - Max) °C 24

(1) EER- og COP-beregning er i henhold til EN14511.
(2) Energimærkningsskala fra A+++ til D. For modeller under 12 kW er SEER og SCOP beregnet på grundlag af værdierne i EU/626/2011. For modeller over 12 kW er SEER og SCOP beregnet på grundlag af værdierne i EU/2281/2016.
(3) Det årlige energiforbrug er beregnet i overensstemmelse med EU/626/2011.
(4) Det viste lydtryk for enhederne er målt 1 m foran hovedkabinettet og 1 m under enheden. Lydtrykket er målt i overensstemmelse med Eurovent 6/C/006-97-specifikationen.
(5) Ved installation af udendørsenheden højere oppe end indendørsenheden.
(6) -20 °C er den laveste temperatur, hvor modellerne 100 ~ 140PZH2E5(8) kan bruges, når rørlængden er op til 30 m.
* Anbefalet sikring til indendørsenheden: 3 A.