Loftsmonterede enheder spreder luften langt og bredt, hvilket er godt i store rum. Højden og dybden er den samme for alle kapaciteter, så enhederne ser ens ud i blandede installationer.

Specifications

See all
PACi Elite loft • R32
12.5 kW
Kit KIT-125PT2ZH8
Remote controller CZ-RTC5B
Cooling capacity (Nominal) kW 12,5
Cooling capacity (Min) kW 3,2
Cooling capacity (Max) kW 14,0
EER (Nominal) (1) W/W 3,45
SEER (2) 6,6
Pdesign (cooling) kW 12,5
Input power cooling (Nominal) kW 3,62
Annual energy consumption cooling (3) kWh/a
Annual energy consumption cooling (3) kWh/a
Heating capacity (Nominal) kW 14,0
Heating capacity (Min) kW 3,2
Heating capacity (Max) kW 16,0
COP (Nominal) (1) W/W 3,99
SCOP (2) 4,4
Pdesign at -10°C kW 9,5
Input power heating (Nominal) kW 3,51
Annual energy consumption heating (3) kWh/a
Indoor unit S-125PT2E5B
Indoor air flow (Hi) m³/min 34,0
Indoor air flow (Med) m³/min 28,0
Indoor air flow (Lo) m³/min 24,0
Indoor sound pressure (Med) (4) dB(A) 40
Indoor sound pressure (Lo) (4) dB(A) 36
Indoor dimension (Height) mm 235
Indoor dimension (Width) mm 1590
Indoor dimension (Depth) mm 690
Indoor net weight kg 40
Outdoor unit U-125PZH2E8
Outdoor power source V 380 - 400 - 415
Current in cooling (1p 220V / 3p 380) A 5,65
Current in cooling (1p 230V / 3p 400) A 5,40
Current in cooling (1p 240V / 3p 415) A 5,20
Current in heating (1p 220V / 3p 380) A 5,50
Current in heating (1p 230V / 3p 400) A 5,20
Current in heating (1p 240V / 3p 415) A 5,05
Outdoor air flow (Cool) m³/min 125
Outdoor air flow (Heat) m³/min 112
Outdoor sound pressure (Cool -Hi) dB(A) 53
Outdoor sound pressure (Heat -Hi) dB(A) 53
Outdoor sound power (Cool -Hi) dB(A) 70
Outdoor sound power (Heat -Hi) dB(A) 70
Outdoor dimension (Height) mm 1416
Outdoor dimension (Width) mm 940
Outdoor dimension (Depth) mm 340
Outdoor net weight kg 99
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88)
Pipe length range m 5 ~ 85
Elevation difference (in/out) (5) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 45
Refrigerant (R32) / CO2 Eq. kg / T 3,05 / 2,059
Operating range (Cool - Min) °C -20 (6)
Operating range (Cool - Max) °C 46
Operating range (Heat - Min) °C -20
Operating range (Heat - Max) °C 24

(1) EER- og COP-beregning er i henhold til EN14511.
(2) Energimærkningsskala fra A+++ til D. For modeller under 12 kW er SEER og SCOP beregnet på grundlag af værdierne i EU/626/2011. For modeller over 12 kW er SEER og SCOP beregnet på grundlag af værdierne i EU/2281/2016.
(3) Det årlige energiforbrug er beregnet i overensstemmelse med EU/626/2011.
(4) Det viste lydtryk for enhederne er målt 1 m foran hovedkabinettet og 1 m under enheden. Lydtrykket er målt i overensstemmelse med Eurovent 6/C/006-97-specifikationen.
(5) Ved installation af udendørsenheden højere oppe end indendørsenheden.
(6) -20 °C er den laveste temperatur, hvor modellerne 100 ~ 140PZH2E5(8) kan bruges, når rørlængden er op til 30 m.
* Anbefalet sikring til indendørsenheden: 3 A.