20.0 kW 25.0 kW 17.92 kW 22.98 kW
Reference PAW-200W5APAC PAW-250W5APAC PAW-200W5APAC-2 PAW-250W5APAC-2
Cooling capacity (1) kW 20,00 25,00 17,92 22,98
EER (1) W/W 3,03 2,89 2,95 2,65
Heating capacity (2) kW 23,00 28,00 23,06 26,00
COP (2) W/W 2,98 2,95 3,69 3,47
ηsh (LOT1) (3) % 178 178 179,8% 176,5%
Energy efficiency class (Scale A+++ to D) (4) A+++ A+++
Water pipe connector Inch Male Thread 1   Male Thread 1   Male Thread 1 ¼ Male Thread 1 ¼
Cooling water flow (∆T=5 K. 35°C) m³/h 3,45 4,30 3,45 4,30
Heating water flow (∆T=5 K. 35°C) L/min 4,15 4,85 4,15 4,85
Flow switch Included Included Included Included
Water filter Included Included Included Included
Outdoor unit U-200PZH2E8 U-250PZH2E8 U-200PZH4E8 U-250PZH4E8
Outdoor sound pressure (Cool -Hi) dB(A) 59 59 57 57
Outdoor sound pressure (Heat -Hi) dB(A) 61 63 61 63
Outdoor dimension (Height) mm 1500 1500 996 996
Outdoor dimension (Width) mm 980 980 1.140 (5) 1.140 (5)
Outdoor dimension (Depth) mm 370 370 460 460
Outdoor net weight kg 117 128 109 109
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52) 1/2 (12,70) 1/2 (12,7) 1/2 (12,7)
Pipe diameter (Gas) Inch (mm) 1 (25,40) 1 (25,40) 7/8 (22,22) 7/8 (22,22)
Pipe length range m 5 ~ 90 5 ~ 60 5 ~ 100 5 ~ 100
Elevation difference (in/out) m 30 30 30 30
Pipe length for additional gas m 30 30 30 30
Additional gas amount g/m 60 80 80 80
Water outlet temperature range (Cool - Min) °C +5 +5 +5 +5
Water outlet temperature range (Cool - Max) °C +15 +15 +15 +15
Water outlet temperature range (Heat - Max) °C +50 +50 +55 +55
Operating range (Cool - Min) °C -15 -15 -15 -15
Operating range (Cool - Max) °C +46 +46 +52 +52
Operating range (Heat - Min) °C -20 -20 -20 -20
Operating range (Heat - Max) °C +24 +24 +35 +35

(1) Data refers to 7°C leaving chilled water temperature and 35°C ambient air temperature, according to EN14511 standard.
(2) Data refers to 35°C leaving warm water temperature and 7°C ambient air temperature according to EN14511 standard.
(3) Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps.
(4) Following COMMISSION REGULATION (EU) No 811/2013 for low-temperature heat pumps. Scale from A+++ to D.