22.98 kW
Reference PAW-250W5APAC-2
Cooling capacity (1) kW 22,98
EER (1) W/W 2,65
Heating capacity (2) kW 26,00
COP (2) W/W 3,47
ηsh (LOT1) (3) % 176,5%
Water pipe connector Inch Male Thread 1 ¼
Cooling water flow (∆T=5 K. 35°C) m³/h 4,30
Heating water flow (∆T=5 K. 35°C) L/min 4,85
Flow switch Included
Water filter Included
Outdoor unit U-250PZH4E8
Outdoor sound pressure (Cool -Hi) dB(A) 57
Outdoor sound pressure (Heat -Hi) dB(A) 63
Outdoor dimension (Height) mm 996
Outdoor dimension (Width) mm 1.140 (5)
Outdoor dimension (Depth) mm 460
Outdoor net weight kg 109
Pipe diameter (Liquid) Inch (mm) 1/2 (12,7)
Pipe diameter (Gas) Inch (mm) 7/8 (22,22)
Pipe length range m 5 ~ 100
Elevation difference (in/out) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 80
Water outlet temperature range (Cool - Min) °C +5
Water outlet temperature range (Cool - Max) °C +15
Water outlet temperature range (Heat - Max) °C +55
Operating range (Cool - Min) °C -15
Operating range (Cool - Max) °C +52
Operating range (Heat - Min) °C -20
Operating range (Heat - Max) °C +35

(1) Data refers to 7°C leaving chilled water temperature and 35°C ambient air temperature, according to EN14511 standard.
(2) Data refers to 35°C leaving warm water temperature and 7°C ambient air temperature according to EN14511 standard.
(3) Following COMMISSION REGULATION (EU) No 813/2013 for low-temperature heat pumps.
(4) Following COMMISSION REGULATION (EU) No 811/2013 for low-temperature heat pumps. Scale from A+++ to D.