PACi Elite adaptive ducted unit - PF3 - R32

Newly designed adaptive ducted unit - PF3 for R32 PACi

2 installation possibilities (horizontal / vertical) with high external static pressure 150Pa allows flexible installation.

Flexibel kanaalmodel PF

De volgende generatie commerciële airconditioners is beschikbaar

Specificaties

Alles zien
PACi Elite adaptive ducted unit - PF3 - R32
10.0 kW
Kit KIT-100PF3ZH25
Remote controller CZ-RTC6
Cooling capacity (Nominal) kW 9,5
Cooling capacity (Min) kW 3,1
Cooling capacity (Max) kW 11,4
EER (Nominal) (1) W/W 4,17
EER (Min) (1) W/W 5,08
EER (Max) (1) W/W 2,82
SEER/ηsc (2) % 7,4 A++
Pdesign (cooling) kW 9,5
Input power cooling (Nominal) kW 2,28
Input power cooling (Min) kW 0,61
Input power cooling (Max) kW 4,04
Annual energy consumption cooling (3) kWh/a 447
Heating capacity (Nominal) kW 10,8
Heating capacity (Min) kW 3,1
Heating capacity (Max) kW 13,5
COP (Nominal) (1) W/W 3,97
COP (Min) (1) W/W 5,25
COP (Max) (1) W/W 3,07
SCOP/ηsc (2) % 4,5 A+
Pdesign at -10°C kW 7,8
Input power heating (Nominal) kW 2,72
Input power heating (Min) kW 0,59
Input power heating (Max) kW 4,40
Annual energy consumption heating (3) kWh/a 2424
Indoor unit S-1014PF3E
External static pressure (Nominal) (4) Pa 40
External static pressure (Min) (4) Pa 10
External static pressure (Max) (4) Pa 150
Moisture removal volume L/h 3,2
Indoor air flow (Hi) m³/min 32,0
Indoor air flow (Med) m³/min 26,0
Indoor air flow (Lo) m³/min 21,0
Indoor sound pressure (Hi) (5) dB(A) 33
Indoor sound pressure (Med) (5) dB(A) 29
Indoor sound pressure (Lo) (5) dB(A) 25
Indoor sound power (Hi) dB(A) 56
Indoor sound power (Med) dB(A) 52
Indoor sound power (Lo) dB(A) 48
Indoor dimension (Height) mm 250
Indoor dimension (Width) mm 1400
Indoor dimension (Depth) mm 730
Indoor net weight kg 39
nanoe X Generator Mark 2
Outdoor unit U-100PZH2E5
Outdoor power source V 220 - 230 - 240
Current in cooling (1p 220V / 3p 380) A 10,30
Current in cooling (1p 230V / 3p 400) A 9,85
Current in cooling (1p 240V / 3p 415) A 9,45
Current in heating (1p 220V / 3p 380) A 12,40
Current in heating (1p 230V / 3p 400) A 11,80
Current in heating (1p 240V / 3p 415) A 11,30
Outdoor air flow (Cool) m³/min 118
Outdoor air flow (Heat) m³/min 108
Outdoor sound pressure (Cool -Hi) dB(A) 52
Outdoor sound pressure (Heat -Hi) dB(A) 52
Outdoor sound power (Cool -Hi) dB(A) 69
Outdoor sound power (Heat -Hi) dB(A) 69
Outdoor dimension (Height) mm 1416
Outdoor dimension (Width) mm 940
Outdoor dimension (Depth) mm 340
Outdoor net weight kg 99
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88)
Pipe length range m 5 ~ 85
Elevation difference (in/out) (6) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 45
Refrigerant (R32) / CO2 Eq. kg / T 3,05 / 2,059
Operating range (Cool - Min) °C -20 (7)
Operating range (Cool - Max) °C +46
Operating range (Heat - Min) °C -20
Operating range (Heat - Max) °C +24
(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12kW, the ηsc / ηsh values is calculated based on EN 14825.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) Medium External static pressure setting from factory.
(5) The sound pressure of the units shows the value measured of the position 1,5m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(6) When installing the outdoor unit at a higher position than the indoor unit.
(7) For models 100~140PZH2E5(8), it is possible to operate the lowest -20°C in the computer rooms with the piping length of 30m or less.
* Recommended fuse for the indoor 3A.
** Above values are in the case of standard installation(horizontal installation in the celling, rear side air intake) and nanoe™ X OFF.