PACi Standard 4 Way 90x90 • R32

Large capacity PACi. Trusted power and high efficiency.

Thanks to advances in design and technology such as the high performance turbo fan, more efficient and silent, the nanoe™ X air cleaner, the U2 Panasonic 4 way 90x90 cassette offers high energy saving, fresh air and comfort.

Bringing nature’s balance indoors

Specifikacije

See all
PACi Standard 4 Way 90x90 • R32
6.0 kW
Kit KIT-60PU2Z5
Remote controller CZ-RTC5B
Cooling capacity (Nominal) kW 6,0
Cooling capacity (Min) kW 2,0
Cooling capacity (Max) kW 7,1
EER (Nominal) (1) W/W 4,00
SEER (2) 7,6 A++
Pdesign (cooling) kW 6,0
Input power cooling (Nominal) kW 1,50
Annual energy consumption cooling (3) kWh/a 276
Heating capacity (Nominal) kW 6,0
Heating capacity (Min) kW 1,8
Heating capacity (Max) kW 7,0
COP (Nominal) (1) W/W 4,72
SCOP (2) 4,7 A++
Pdesign at -10°C kW 6,0
Input power heating (Nominal) kW 1,27
Annual energy consumption heating (3) kWh/a 1787
Indoor unit S-60PU2E5B
Indoor air flow (Hi) m³/min 21,0
Indoor air flow (Med) m³/min 16,0
Indoor air flow (Lo) m³/min 13,0
Moisture removal volume L/h 1,7
Indoor sound pressure (Med) (4) dB(A) 31
Indoor sound pressure (Lo) (4) dB(A) 28
Indoor sound power (Hi) dB(A) 51
Indoor sound power (Med) dB(A) 46
Indoor sound power (Lo) dB(A) 43
Indoor dimension (Height) mm 256
Indoor dimension (Width) mm 840
Indoor dimension (Depth) mm 840
Panel dimension (Height) mm 33,5
Panel dimension (Depth) mm 950
Indoor net weight kg 20
Panel net weight kg 5
nanoe X Generator Mark 1
Outdoor unit U-60PZ2E5
Outdoor power source V 220 - 230 - 240
Current in cooling (1p 220V / 3p 380) A 7,40
Current in cooling (1p 230V / 3p 400) A 7,05
Current in cooling (1p 240V / 3p 415) A 6,75
Current in heating (1p 220V / 3p 380) A 6,25
Current in heating (1p 230V / 3p 400) A 5,95
Current in heating (1p 240V / 3p 415) A 5,70
Outdoor air flow (Cool) m³/min 40
Outdoor air flow (Heat) m³/min 45
Outdoor sound pressure (Cool -Hi) dB(A) 46
Outdoor sound pressure (Heat -Hi) dB(A) 48
Outdoor sound power (Cool -Hi) dB(A) 65
Outdoor sound power (Heat -Hi) dB(A) 68
Outdoor dimension (Height) mm 695
Outdoor dimension (Width) mm 875
Outdoor dimension (Depth) mm 320
Outdoor net weight kg 44
Pipe diameter (Liquid) Inch (mm) 3/8 (9,52)
Pipe diameter (Gas) Inch (mm) 5/8 (15,88)
Pipe length range m 3 ~ 40
Elevation difference (in/out) (5) m 30
Pipe length for additional gas m 30
Additional gas amount g/m 35
Refrigerant (R32) / CO2 Eq. kg / T 1,45 / 0,979
Operating range (Cool - Min) °C -10
Operating range (Cool - Max) °C 43
Operating range (Heat - Min) °C -15
Operating range (Heat - Max) °C 24

(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the SEER and SCOP is calculated based on values of EU/2281/2016.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) The sound pressure of the units shows the value measured of the position 1,5 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(5) When installing the outdoor unit at a higher position than the indoor unit.
* Recommended fuse for the indoor 3 A.