PACi Elite High Static Pressure Hide Away • R32
The ducted systems are the ideal solution for flexible, concealed air conditioning and the optional 200mm spigots ensure simple, hassle-free connection to spiral ductwork.
Specifikacije
PACi Elite High Static Pressure Hide Away • R32 | |||
---|---|---|---|
12.5 kW | |||
EER (Nominal) (1) | W/W | 3,56 | |
COP (Nominal) (1) | W/W | 3,48 | |
Refrigerant (R32) / CO2 Eq. | kg / T | — | |
EER (Nominal) (1) | W/W | 3,56 | |
COP (Nominal) (1) | W/W | 3,48 | |
External static pressure (Nominal) (4) | Pa | 100 | |
External static pressure (Min) (4) | Pa | 10 | |
External static pressure (Max) (4) | Pa | 150 | |
Indoor sound pressure (Hi) (5) | dB(A) | 39 | |
Indoor sound pressure (Med) (5) | dB(A) | 35 | |
Indoor sound pressure (Lo) (5) | dB(A) | 32 | |
Elevation difference (in/out) (6) | m | 30 | |
Refrigerant (R32) / CO2 Eq. | kg / T | — |
(1) EER and COP calculation is based in accordance to EN14511.
(2) Energy Label Scale from A+++ to D. For models below 12 kW, the SEER and SCOP is calculated based on values of EU/626/2011. For models above 12 kW, the SEER and SCOP is calculated based on values of EU/2281/2016.
(3) The annual energy consumption is calculated in accordance to EU/626/2011.
(4) Medium External static pressure setting from factory.
(5) The sound pressure of the units shows the value measured of the position 1,5 m below the unit. The sound pressure is measured in accordance with Eurovent 6/C/006-97 specification.
(6) When installing the outdoor unit at a higher position than the indoor unit.
(7) For models 100 ~ 140PZH2E5(8), it is possible to operate the lowest -20 °C in the computer rooms with the piping length of 30 m or less.
* Recommended fuse for the indoor 3 A.